■Wiring selection of output
Set the wiring selection of output.
Address
Name
(hexadecimal)
0180H to 0181H
Wiring selection of output
Address: 0180H
b15
b14
b13
b12
Wiring selection of output Y3
Address: 0181H
b15
b14
b13
b12
Wiring selection of output Y7
• When double output is set for Yn (n = 0, 2, 4, 6) of double output, only double output can be selected for
Yn+1.
• When double output is set, outputting on of a pair of outputs turns on the output signal.
• When setting double output, if Yn (n: even number) is set to double wiring (source/source), set the same
value as Yn for Yn+1 in the output dark test execution setting.
• For unused output terminals, set "0: Not used" in the wiring selection of output.
■Output dark test execution setting
Set whether to perform the output dark test function of the diagnostic function in the safety remote I/O module.
Address
Name
(hexadecimal)
0190H
Output dark test execution setting
b15
b14
b13
b12
0 (fixed)
When "0: Not used" is selected in the wiring selection of output, this parameter will be ignored.
■Output dark test pulse OFF time
Set the width of the OFF pulses used for an output dark test.
Address
Name
(hexadecimal)
01A0H to 01A7H
Output dark test pulse OFF time
When "0: Not used" is selected in the wiring selection of output, or "1: Do not perform" is selected in the output
dark test execution setting, this parameter will be ignored.
b11
b10
b9
b8
Wiring selection of output Y2
b11
b10
b9
b8
Wiring selection of output Y6
b11
b10
b9
b8
Setting range
0: Not used
1: Double wiring (Source/Source)
2: Single wiring
b7
b6
b5
b4
Wiring selection of output Y1
b7
b6
b5
b4
Wiring selection of output Y5
Setting range
0: Perform
1: Do not perform
b7
b6
b5
b4
Y7
Y6
Y5
Y4
Setting range
0: 400s
1: 1ms
2: 2ms
Appendix 4 Remote Buffer Memory
Default value
0000H
b3
b2
b1
b0
Wiring selection of output Y0
b3
b2
b1
b0
Wiring selection of output Y4
Default value
0000H
b3
b2
b1
b0
Y3
Y2
Y1
Y0
Default value
0000H
APPX
189
A