Performance Specifications - Mitsubishi Electric NZ2GFSS2 32D S1 User Manual

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

3.2

Performance Specifications

NZ2GFSS2-32D-S1 type main input module
Item
CC-Link IE station type
Number of input points
*2
Rated input voltage
Rated input current
Isolation method
Max. number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input circuit response time
Safety remote station refresh response processing time
Input response time of safety remote station
External power supply for
*2
input part
Power supply current for input device (COM+)
Input type
Withstand voltage
Isolation resistance
Noise immunity
Protection degree
Wiring method for common
External interface
Applicable DIN rail
Applicable wire size
Applicable solderless
terminal
Cyclic transmission
Applicable safety protocol version
Communication cable
Availability of connecting extension module
3 SPECIFICATIONS
20
3.2 Performance Specifications
OFF  ON
ON  OFF
Voltage
Current
Protection function
Fuse
Communication part
Module power supply part
Input part, external power supply
part
Terminal block for module power
supply and FG
I/O terminal block
Terminal block for module power
*1
supply and FG
I/O terminal block
RX/RY points
RWr/RWw points
SA\X/SA\Y points
NZ2GFSS2-32D-S1
Remote device station
Single wiring: 32 points, double wiring: 16 points
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
6.0mA TYP. (24VDC)
Photocoupler isolation
100% (horizontal installation), when any installation method other than the horizontal
installation is performed, refer to the derating chart.
15VDC or higher/2mA or higher
5VDC or lower/0.5mA or lower
Approx. 2.0k
0.4ms or less (24VDC)
0.4ms or less (24VDC)
2.0ms
Input circuit response time + Input response time (1ms, 5ms, 10ms, 20ms, 50ms)
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
40mA
External power supply overvoltage protection function, external power supply
overcurrent protection function
8A (user-unchangeable)
0.4A/1 terminal
Negative common
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and ground (500VDC isolation
resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise
simulator condition)
IP2X
Input 32 points/common (2-piece spring clamp terminal block)
RJ45 connector
Terminal block for module power supply and FG (2-piece spring clamp terminal block)
40 points, 2-piece spring clamp terminal block (push-in)
TH35-7.5Fe, TH35-7.5A (compliant with JIS C 2812/IEC 60715)
Core: 0.5 to 2.0 (20 to 14 AWG), terminal hole size: 2.8mm  2.0mm
Core: 0.3 to 1.5 (22 to 16 AWG), terminal hole size: 2.4mm  1.5mm
Page 59 List of bar solderless terminals
Page 65 List of bar solderless terminals
80 points
32 points
64 points
2 (fixed)
An Ethernet cable that meets the 1000BASE-T standard: Category 5e or higher (double
shielded, STP), straight cable
Connectable

Hide quick links:

Advertisement

Table of Contents
loading