Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 159

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Error code
Safety error subset code
(hexadecimal)
Error
classification
8402H
311
8403H
450
8404H
450
8405H
311
8406H
450
8407H
450
Classification
Error item
number
(hexadecimal)
0001H
Communication
error
8403H
Communication
error
8404H
Communication
error
0000H
Communication
error
8406H
Communication
error
8407H
Communication
error
Error name
Description
and cause
Safety
Response
communication
monitoring timeout
connection being
was detected while
established
the safety
Response
connection was
monitoring
being established
timeout
in the safety
communication
with the master
station.
Safety
Response
communication
monitoring timeout
being refreshed
was detected while
Response
the safety
monitoring
communication
timeout
was being
refreshed in the
safety
communication
with the master
station.
Safety
Response
communication
monitoring timeout
error in
was detected while
processing
a safety
Response
communication
error was being
monitoring
timeout
processed in the
safety
communication
with the master
station.
Safety
Receiving interval
communication
monitoring timeout
receiving interval
was detected in the
monitoring
safety
timeout
communication
with the master
station.
Safety
Unacceptable
communication
delay was detected
receive data
in the analysis of
delay detection
the data received
from the master
station.
Safety
A loss was
communication
detected in the
receive data loss
analysis of the data
detection
received from the
master station.
Action
• Correct "Sending Interval
Monitoring Time" of the module
parameter as well as "Safety
Communication Setting" of the
master station. After that, refer to
the following and set module
parameters and perform the
safety module validation
according to the parameter
setting procedure. (Page 68
VARIOUS SETTINGS)
• When the parameter setting has
no errors, there may be an
influence from noise or a
hardware failure. If the same
error occurs again even after
measures have been taken
against noise, the module may
be in failure. Please consult your
local Mitsubishi representative.
10 TROUBLESHOOTING
157
10.7 List of Error Codes
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents