Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 141

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Error code
Safety error subset code
(hexadecimal)
Error
classification
0105H
450
0106H
450
0107H
450
0108H
450
0109H
450
0201H
450
*1
0202H
450
0203H
450
Classification
Error item
number
(hexadecimal)
0105H
Moderate error
0106H
Moderate error
0107H
Moderate error
0108H
Moderate error
0109H
Moderate error
0201H
Minor error
Recoverable
0202H
Minor error
Recoverable
0203H
Minor error
Recoverable
Error name
Description and
cause
Date out of
Incorrect clock data
range error
was received from
the CPU module.
Improper
A module that
module
cannot be used for
connected
extension is
connected.
Safety module
The safety module
validation not
validation has not
performed
been performed.
Restart not
The module has not
performed after
been restarted after
safety module
the safety module
validation
validation.
Module power
A module power
supply voltage
supply error was
error
detected.
Non-volatile
The error history
memory data
data stored in the
error (error
non-volatile memory
history)
is incorrect.
Remote buffer
An area outside the
memory access
range of the remote
error
buffer memory
areas has been
accessed using the
REMFR/REMTO
instructions.
Station number
The station number
switch changed
setting switches
error
have been changed
while the module
power supply is on.
Action
There may be an influence from
noise or a hardware failure. If the
same error occurs again even after
measures have been taken against
noise, the module may be in
failure. Please consult your local
Mitsubishi representative.
Check whether the extension
module connected is connectable
to this product. If the module is
connectable, there may be an
influence from noise or a hardware
failure. If the same error occurs
again even after measures have
been taken against noise, the
module may be in failure. Please
consult your local Mitsubishi
representative.
• Perform the safety module
validation and restart the
module.
• If the same error occurs again,
the module may be in failure.
Please consult your local
Mitsubishi representative.
• Restart the module.
• If the same error occurs again,
the module may be in failure.
Please consult your local
Mitsubishi representative.
• Review the connected devices,
wiring, and voltage.
• If the same error occurs again,
the module may be in failure.
Please consult your local
Mitsubishi representative.
• The module will automatically
recover immediately after the
error occurs. Note that the error
history of the errors that have
occurred will be lost.
• If the same error occurs again,
the module may be in failure.
Please consult your local
Mitsubishi representative.
Correct the setting data of the
REMFR/REMTO instruction to
access within the range of remote
buffer memory areas.
The module will recover from this
error by setting the switches to the
previous station number that was
set when the module power supply
was powered on.
10 TROUBLESHOOTING
139
10.7 List of Error Codes
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents