Unit
Item
Basic module
Wiring selection of input
parameter_main
module
Input response time [main
module]
Double input discrepancy
detection setting
Double input discrepancy
detection type
Double input discrepancy auto recovery setting
Double input discrepancy
detection time
Input dark test execution
setting
Input dark test pulse OFF time setting
Number of pulse output for input dark test
Wiring selection of output
Output dark test execution
setting
Output dark test pulse OFF
time setting
Number of pulse output for
output dark test
Number of ON times
integration function enable
• Set all the items of the parameters displayed. If any item is left blank, the parameters cannot be written to
the safety remote I/O module.
• For the monitoring area of the standard extension module, refer to the following.
 CC-Link IE Field Network Remote I/O Module User's Manual
Wiring selection of input X0 to Wiring
selection of input X7
Input response time X0 to Input
response time X7
Double input discrepancy detection
setting X0/X1 to Double input
discrepancy detection setting X6/X7
Double input discrepancy detection
type X0/X1 to Double input
discrepancy detection type X6/X7
Double input discrepancy detection
time X0/X1 to Double input
discrepancy detection time X6/X7
Input dark test execution setting X0
to Input dark test execution setting
X7
Wiring selection of output Y0 to
Wiring selection of output Y7
Output dark test execution setting
Y0 to Output dark test execution
setting Y7
Output dark test pulse OFF time
setting Y0 to Output dark test pulse
OFF time setting Y7
Number of pulse output for output
dark test Y0 to Number of pulse
output for output dark test Y7
Number of ON times integration
function enable Y0 to Number of ON
times integration function enable Y7
Setting range
Reference
0: Not used (default)
Page 85 Safety input wiring
1: Double wiring (NC/NC)
selection function
2: Single wiring
0: 1.0ms (default)
Page 88 Safety input
1: 1.5ms
response time setting
2: 5ms
function
3: 10ms
4: 20ms
5: 50ms
6: 70ms
0: Detect (default)
Page 93 Double input
1: Do not detect
discrepancy detection
function
0: Discrepancy detection time
specified (default)
1: Discrepancy detection time not
specified
0: Not used (default)
1: Used
1 to 6000 (default: 1)  10ms
0: Perform (default)
Page 101 Input dark test
1: Do not perform
function
0: 400s (default)
1: 1ms
2: 2ms
0: 1 time (default)
1: 2 times
2: 3 times
0: Not used (default)
Page 89 Safety output wiring
1: Double wiring (Source/Source)
selection function
2: Single wiring
0: Perform (default)
Page 105 Output dark test
1: Do not perform
function
0: 400s (default)
1: 1ms
2: 2ms
0: 1 time (default)
1: 2 times
2: 3 times
0: Disable (default)
Page 92 Number of safety
1: Enable
output ON times integration
function
7 VARIOUS SETTINGS
7.2 Parameter Settings
7
77

Hide quick links:

Advertisement

Table of Contents