Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 194

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Monitoring area
■Number of ON times integration value
This area stores the integration value of the number of ON times integration function. ( Page 92 Number of safety output
ON times integration function)
• NZ2GFSS2-8TE-S1, NZ2GFSS2-16DTE-S1
Address
Name
(hexadecimal)
0610H to 061FH
Number of ON times integration value Y0 to Y7
■Double input discrepancy auto recovery enabled signal
This signal stores the status of the auto recovery setting enabled signal when a double input discrepancy detection error
occurs. This signal turns on when "Double input discrepancy auto recovery setting" is set to "1: Used". This signal becomes
effective when the mode is switched to the safety operation mode.
• NZ2GFSS2-32D-S1
Address
Name
(hexadecimal)
0700H
Double input discrepancy auto recovery enabled signal
■Double input discrepancy detection state
When "Double input discrepancy auto recovery setting" is set to "1: Used", the detection status of a double input discrepancy
error is stored. This area turns on when a double input discrepancy detection error has occurred in a pair of the corresponding
input signals.
• NZ2GFSS2-32D-S1
Address
Name
(hexadecimal)
0701H
Double input discrepancy detection state
b15
b14
b13
X1E
X1C
X1A
X1F
X1D
X1B
APPX
192
Appendix 4 Remote Buffer Memory
b12
b11
b10
b9
X18
X16
X14
X12
X19
X17
X15
X13
Setting range
0 to 2147483647
Setting range
0: Not used
1: Used
Setting range
0: Not detected
1: Detected
b8
b7
b6
b5
X10
XE
XC
XA
X11
XF
XD
XB
Default value
0
Default value
0000H
Default value
0000H
b4
b3
b2
b1
X8
X6
X4
X2
X9
X7
X5
X3
b0
X0