■Number of pulse output for output dark test
Set the number of pulse output for output dark test.
Address
Name
(hexadecimal)
01B0H to 01B7H
Number of pulse output for output dark test
When "0: Not used" is selected in the wiring selection of output, or "1: Do not perform" is selected in the output
dark test execution setting, this parameter will be ignored.
■Number of ON times integration function enable
Set the number of ON times integration function enable.
Address
Name
(hexadecimal)
01C0H
Number of ON times integration function enable
b15
b14
b13
0 (fixed)
When "0: Not used" is selected in the wiring selection of output, this parameter will be ignored.
■Extension module identification code
Set the identification code for specifying the extension module type of the NZ2GFSS2-8D-S1, NZ2GFSS2-8TE-S1, or
NZ2GFSS2-16DTE-S1.
Address
Name
(hexadecimal)
0200H
Extension module identification code
b15
b14
b13
Module type
00H: Extension module not connected
01H: Digital input module
02H: Digital output module
The NZ2EXSS2-8TE cannot be connected to the NZ2GFSS2-8D-S1, NZ2GFSS2-8TE-S1, or NZ2GFSS2-
16DTE-S1.
APPX
190
Appendix 4 Remote Buffer Memory
b12
b11
b10
b9
b12
b11
b10
b9
Setting range
0: 1 time
1: 2 times
2: 3 times
Setting range
0: Disable
1: Enable
b8
b7
b6
b5
Y7
Y6
Y5
Setting range
000H: Extension module not connected
0101H: 16-points digital input module
0201H: 16-points digital output module
b8
b7
b6
b5
Points
01H: 16 points
Default value
0000H
Default value
0000H
b4
b3
b2
b1
Y4
Y3
Y2
Y1
Default value
0000H
b4
b3
b2
b1
b0
Y0
b0