Setting procedure
The following shows the procedure to set module parameters of the master station from the "Network Configuration Settings"
window.
When the user authentication function of the CPU module is enabled, perform the logon of the user
authentication function in advance. For the user authentication function, refer to the following.
Page 109 User Authentication Function
Operating procedure
1.
For preparation before setting module parameters, follow the steps below.
• Connect the safety remote I/O module to a network and power on the module.
• Connect the engineering tool to the CPU module of the master station.
• Build the module configuration in the engineering tool. For details on the setting, refer to the following.
 GX Works3 Operating Manual
• Set the Safety CPU to the test mode. For details on the setting, refer to the following.
 GX Works3 Operating Manual
2.
Display the "CC IE Field Configuration" window.
[Navigation window]  [Parameter]  [Module Information]  Model name  [Basic Settings]  [Network Configuration
Settings]  "CC IE Field Configuration" window
7 VARIOUS SETTINGS
70
7.1 Network Configuration Settings