Details Of Remote Control/Monitor Signals - Mitsubishi Electric NZ2GFSS2 32D S1 User Manual

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Details of remote control/monitor signals

Warning status flag
■Device No.
Model
NZ2GFSS2-32D-S1
NZ2GFSS2-8D-S1
NZ2GFSS2-8TE-S1
NZ2GFSS2-16DTE-S1
■Description
Warning status flag (RX) turns on when a minor error occurs. Five seconds after the cause of the minor error is eliminated,
0000H is automatically stored in Warning code (RX) and Warning status flag (RX) turns off.
Ex.
For the NZ2GFSS2-32D-S1 and NZ2EXSS2-8TE
A minor error
occurred.
Warning code
(RX20 to RX2F)
Warning status flag
(RX7)
OFF
ON
Remote READY
(RXB)
Controlled by the safety remote I/O module
APPX
172
Appendix 2 Remote Control/Monitor Signals
Name
Warning status flag
0000H
Error code
ON
The minor error is
removed.
5 seconds
OFF
Device No.
RX7
RXC
0000H