6.4

Wiring

Wiring of terminal block for module power supply and FG

Tightening torque
Tighten the terminal block mounting screws within the following specified torque range. Tightening the screws too much may
damage the module case.
Screw type
Terminal block mounting screw (M2.5 screw)
Wire to be used
The following table lists the wires to be connected to the terminal block for module power supply and FG. When using the
safety remote I/O module as a UL listed product, use the following wires.
Module model name
NZ2GFSS2-32D-S1
NZ2GFSS2-8D-S1, NZ2GFSS2-8TE-S1,
NZ2GFSS2-16DTE-S1
Installing and removing the terminal block
To remove the terminal block, loosen the terminal block mounting screws with a flathead screwdriver and pull out the terminal
block.
To install the terminal block, insert the terminal block into the connector and securely fix the terminal block with the terminal
block mounting screws. Failure to secure the terminal block may cause drop, short circuit, malfunction.
Tightening torque range
0.2 to 0.3Nm
Diameter
Type
Material
20 to 14 AWG
Stranded wire
Copper wire
22 to 16 AWG
Stranded wire
Copper wire
Temperature rating
Stripping length of the cable
75 or higher
10mm
75 or higher
10mm