7.1

Network Configuration Settings

The following parameters are required to use the safety remote I/O module. The parameters are automatically set when a
main module is added in the "Network Configuration Settings". Change the start number and end number of the RX/RY
Setting or RWr/RWw Setting as necessary.
Item
STA#
Station Type
RX/RY Setting
RWw/RWr Setting
• When using the safety remote I/O module, always enable "Station-based Block Data Assurance" of the
master station. When it is disabled, correct operation of the safety remote I/O module cannot be
guaranteed. For the station-based block data assurance, refer to the following.
 MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)
• Do not set the module parameters using the CCPASET instruction in the master station. Correct operation
of the safety remote I/O module cannot be guaranteed because the module operates with the Station-based
Block Data Assurance disabled when the CCPASET instruction is executed.
• Even though the number of points in the RX/RY Setting or RWw/RWr Setting and that in a main module or
an extension module differ, an error does not occur on the module. For example, when the number of points
in the RX/RY Setting is set to 16 in a configuration with a main module and extension module, only the first
16 points are refreshed.
Points
Points
Description
Set the station number of the safety remote I/O module.
Set "Remote Device Station".
80 points
32 points
7.1 Network Configuration Settings
7 VARIOUS SETTINGS