Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 23

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Item
*2
Module power supply
Voltage
Current
Protection function
Fuse
Allowable momentary power failure
time
Weight
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*2 For the power supply to be connected to the main module or the power supply of the devices to be connected to the input part, use the
product that meets the following conditions:
 SELV (Safety Extra Low Voltage)
 LVD (Low Voltage Directive)-compliant product
 LIM (Limited Energy Circuit) or UL 1310 Class 2 compliant
 Output voltage specifications: 24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
*3 When an extension module is connected, the current consumption of the extension module is added.
*4 At a momentary power failure over 10ms, the module operates as any of the following.
 The operation remains.
 The input and output are turned off by the protection circuit, and the communication is disabled. To recover the module, power off and
on the module power supply.
 The module is restarted and initialized. The operation is the same as when the module power supply is powered off and on.
In the case other than when the operation remains, the safety station interlock status is applied. Cancel the safety station interlock of the
CPU module. For the safety station interlock, refer to the following.
 MELSEC iQ-R CPU Module User's Manual (Application)
■Derating chart (except horizontal installation)
32
28
24
20
Maximum number
of simultaneous
16
ON points (point)
Input voltage
12
24VDC
8
26.4, 28.8VDC
4
0
0
10
NZ2GFSS2-32D-S1
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
*3
230mA
Module power supply overvoltage protection function, module power supply overcurrent
protection function
1.6A (user-unchangeable)
Within 10ms
*4
0.45kg
20
30
40
Ambient temperature (°C)
50
3.2 Performance Specifications
3 SPECIFICATIONS
21
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents