Output Y OFF information
■Device No.
Name
Output Y OFF information
■Description
Whether output Y has been turned off or not can be checked with Output Y OFF information (RWr1F).
The amount of time delay from when Output Y OFF information (RWr1F) changes until the external output accordingly
changes is not more than output response time.
b15
b14
b13
YF
YE
YD
Off: Output Y has never been turned off.
On: Output Y has been turned off.
Output Y OFF information (RWr1F) can be cleared by using Output Y OFF information clear request
(RWw1F).
Output Y ON information clear request
■Device No.
Name
Output Y ON information clear request
■Description
This remote register area is used to clear Output Y ON information (RWr1C).
Clear processing continues while the bit of Output Y ON information clear request (RWw1C) is on.
b15
b14
b13
YF
YE
YD
Off: Output Y ON information is not cleared.
On: Output Y ON information is cleared.
For the timing of turning on and off the remote register, refer to the following.
Remote output signal RY0
External output signal Y0
Output Y ON information Y0
(RWr1C.b0)
Output Y ON information
clear request Y0 (RWw1C.b0)
(1) Remains on even after Y0 turns off.
(2) Turns off when the clear request turns on.
Controlled by the safety remote I/O module
Controlled by the program
APPX
176
Appendix 3 Remote Register
b12
b11
b10
b9
YC
YB
YA
Y9
b12
b11
b10
b9
YC
YB
YA
Y9
ON
OFF
OFF
ON
OFF
ON
OFF
(1)
OFF
Device No.
RWr1F
b8
b7
b6
b5
Y8
Y7
Y6
Y5
Device No.
RWw1C
b8
b7
b6
b5
Y8
Y7
Y6
Y5
OFF
b4
b3
b2
b1
Y4
Y3
Y2
Y1
b4
b3
b2
b1
Y4
Y3
Y2
Y1
(2)
OFF
ON
OFF
b0
Y0
b0
Y0