<When the module shifts to the safety operation mode>
Module operation mode
External power supply status
<When an external power supply voltage error has occurred>
Module operation mode
External power supply status
External power supply status
(SA\X2D)
Safety output control READY
(SA\X2E)
Safety output control initial
processing request flag (SA\Y2E)
Safety output control start flag
(SA\Y2F)
Safety output control initial
processing completion flag
(SA\X2F)
Test pulse output terminal
(T0 to T3)
Output signal
(Y…/Y…+1)
(1) After checking that External power supply status is on, turn on Safety output control initial processing request flag (SA\Y2E) so that Safety output control
initial processing completion flag (SA\X2F) turns on.
(2) After checking that Safety output control initial processing completion flag (SA\X2F) is on, turn off Safety output control initial processing request flag
(SA\Y2E) so that Safety output control initial processing completion flag (SA\X2F) turns off.
(3) After checking that Safety output control initial processing completion flag (SA\X2F) is off, turn on Safety output control start flag (SA\Y2F) so that Safety
output control READY (SA\X2E) turns on.
(4) After checking that Safety output control READY (SA\X2E) is on, turn off Safety output control start flag (SA\Y2F).
(5) Safety output control READY (SA\X2E) turns on, and safety outputs and test pulse outputs start.
Controlled by the safety remote I/O module
Controlled by the program
*1 An external power supply voltage error has not occurred.
*2 An external power supply voltage error has occurred.
Setting method
To select what operation is to be performed at the detection of an external power supply voltage error, set the operation in
"Operation setting of external power supply voltage error detection" on the "Parameter Processing of Device Station" window
of the engineering tool.
For the procedure to display the "Parameter Processing of Device Station" window, refer to the following.
Page 72 Parameter Settings
Item
Operation setting of external power supply voltage error detection
8 FUNCTIONS
116
8.7 Operation Setting Function at Detection of External Power Supply Voltage Error
Standby mode
Safety operation mode
*2
Error
ON
OFF
OFF
ON
OFF
(2)
OFF
ON
OFF
OFF
OFF
Safety operation mode
*1
Normal
*1
Normal
(1)
ON
OFF
ON
(3)
OFF
ON
ON
Setting range
0: Stop safety communication
1: Continue safety communication (Without output interlock)
2: Continue safety communication (With output interlock)
(4)
OFF
(5)