Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 33

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Item
Cyclic transmission
RX/RY points
RWr/RWw points
SA\X/SA\Y points
Applicable safety protocol version
Communication cable
Availability of connecting extension module
*2*4
Module power supply
Voltage
Current
Protection function
Fuse
Safety element
Weight
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*2 For the power supply to be connected to the main module or the power supply of the devices to be connected to the input part, use the
product that meets the following conditions:
 SELV (Safety Extra Low Voltage)
 LVD (Low Voltage Directive)-compliant product
 LIM (Limited Energy Circuit) or UL 1310 Class 2 compliant
 Output voltage specifications: 24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
*3 When an extension module is connected, the current consumption of the extension module is added.
*4 To connect to the module, use a power supply whose output hold time is 10ms or longer.
*5 The voltage at OFF is calculated as follows: resistance value of the connected load  leakage current at off.
NZ2GFSS2-16DTE-S1
80 points
32 points
32 points
2 (fixed)
An Ethernet cable that meets the 1000BASE-T standard: Category 5e or higher (double
shielded, STP), straight cable
Connectable
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
*3
160mA
Module power supply overvoltage protection function, module power supply overcurrent
protection function
1.6A (user-unchangeable)
Type B, HFT = 1, SC 3
0.25kg
3 SPECIFICATIONS
3.2 Performance Specifications
3
31