Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 78

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

■NZ2GFSS2-16DTE-S1
Unit
Item
Station parameter
Safety setting
I/O LED indication setting at error occurrence
Cyclic data update monitoring time setting
Extension I/O setting
Operation setting of external power supply voltage error detection
7 VARIOUS SETTINGS
76
7.2 Parameter Settings
Transmission interval monitoring
time
Input response time setting
Output HOLD/CLEAR setting
Setting range
4 to 1000ms (default: 35)
0: No indication of error point
(default)
1: Indication of error point
0 to 20 (default: 0)  100ms
0: 0ms
1: 0.2ms
2: 1.0ms
3: 1.5ms
4: 5ms
5: 10ms (default)
6: 20ms
7: 70ms
0: CLEAR (default)
1: HOLD
0: Stop safety communication
(default)
1: Continue safety
communication (Without output
interlock)
2: Continue safety
communication (With output
interlock)
Reference
Page 37 Safety remote I/O
module safety response time
Page 110 Operation Setting
Function at Detection of
External Power Supply
Voltage Error

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents