9.2

Periodic Inspection

This section describes items that must be inspected one or two times every six months to one year. When the equipment has
been relocated or modified, or cable laying has been changed, inspect the module for the items.
Item
Inspection item
1
Environment
Ambient
temperature
Ambient humidity
Atmosphere
2
Power supply voltage check
3
Mounting status
Rattling
on a DIN rail
Terminal block
Looseness and
mounting screw
rattling
Terminal block
Attachment of dirt
condition
and foreign
matters
4
Connection
Clearance
status
between
solderless
terminals
*1 The temperature in the control panel where the safety remote I/O module is installed
Inspection method
Measure the temperature by using
*1
a thermometer.
Measure the humidity by using a
hygrometer.
Measure corrosive gases.
Measure the voltage across
24VDC terminals.
Check for a rattling noise of the
safety remote I/O module.
Check for the looseness of terminal
block mounting screws.
Check for attachment of dirt and
foreign matters.
Check the clearance between
solderless terminals.
Judgment criterion
Corrective action
0 to 55
Create the environment that satisfies
the judgment criterion
5 to 95%RH
No corrosive gases
20.4 to 28.8VDC
Change the supply power.
The safety remote I/O
Remount the safety remote I/O
module does not rattle.
module on the DIN rail securely.
The terminal block
Retighten terminal block mounting
mounting screws must not
screws securely.
be loose.
Dirt and foreign matters
Remove the terminal block and clean
must not be attached to
it.
terminal blocks.
The proper clearance must
Provide the proper clearance.
be provided between
solderless terminals.
9 MAINTENANCE AND INSPECTION
9.2 Periodic Inspection
9
121

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents