6.
After writing parameters is completed, visually check that the module parameters have been normally written to the
module. To check the module parameters, refer to the following.
 GX Works3 Operating Manual
7.
Perform the operations from "Parameter write" to the visual check of the module parameters for all safety remote I/O
modules connected.
8.
Set the module parameter of the master station "To Use of Not to Use the Safety Communication Setting" to "Use".
[Module Parameter]  [Application Settings]  [Safety Communication Setting]  [To Use of Not to Use the Safety
Communication Setting]
9.
Select "Detailed Setting" of the module parameter of the master station "Safety Communication Setting" and the "Safety
Communication Setting" window is displayed.
[Module Parameter]  [Application Settings]  [Safety Communication Setting]  [Safety Communication Setting]
7 VARIOUS SETTINGS
80
7.2 Parameter Settings