Continue safety communication (With output interlock)
■Output interlock
In the following cases, the outputs are interlocked.
• Module operation mode is switched from standby mode to safety operation mode.
• Safety outputs are turned off due to an external power supply voltage error detection.
If the outputs are interlocked, the safety output control stops and the output signals (Y) are turned off.
The safety output control does not start until the safety output interlock is canceled by the CPU module. This prevents an
incorrect output before completion of checking safety in the working area and an incorrect output due to unintended recovery
of the external power supply.
Ex.
For the NZ2GFSS2-32D-S1 (when the module shifts to the safety operation mode)
Module operation mode
Status of the external power
supply
External power supply status
(SA\X2D)
Safety output control READY
(SA\X2E)
Test pulse output terminal
(T0 to T3)
Output signal
(Y…/Y…+1)
(1) Outputs are interlocked and each signal remains off.
Controlled by the safety remote I/O module
*1 An external power supply voltage error has not occurred.
Ex.
For the NZ2GFSS2-32D-S1 (when an external power supply voltage error has occurred)
Module operation mode
Status of the external power
supply
External power supply status
(SA\X2D)
Safety output control READY
(SA\X2E)
Test pulse output terminal
(T0 to T3)
Output signal
(Y…/Y…+1)
(1) If an external power supply voltage error occurs, Safety output control READY (SA\X2E) turns off and safety outputs and test pulse outputs stop.
Controlled by the safety remote I/O module
*1 An external power supply voltage error has not occurred.
*2 An external power supply voltage error has occurred.
8 FUNCTIONS
114
8.7 Operation Setting Function at Detection of External Power Supply Voltage Error
Standby mode
ON
OFF
OFF
OFF
OFF
Safety operation mode
Normal
ON
ON
ON
ON
Safety operation mode
*1
Normal
OFF
(1)
*1
OFF
OFF
OFF
OFF
*2
Error
(1)