Error Codes Related To Safety Communication - Mitsubishi Electric NZ2GFSS2 32D S1 User Manual

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Error codes related to safety communication

The following table lists safety communication error codes.
The ERR LED does not turn on when a communication error related to the safety communication occurs, the same as a case
when a communication error of the CC-Link IE Field Network occurs. When an error occurs, the SAFETY LED turns off and
the D LINK LED does not change.
Error code
Safety error subset code
(hexadecimal)
Error
classification
8400H
310
450
312
8401H
450
10 TROUBLESHOOTING
156
10.7 List of Error Codes
Classification
Error item
number
(hexadecimal)
0001H
Communication
error
0002H
8400H
0000H
8401H
Communication
error
Error name
Description
and cause
Safety
An error was
communication
detected in the
error
safety
communication
with the master
station.
Safety
A communication
communication
interrupt has
disabled due to a
occurred on CC-
communication
Link IE Field
interrupt
Network and the
safety
communication is
stopped.
Action
• Refer to the following and set
module parameters and perform
the safety module validation
according to the parameter
setting procedure. ( Page 68
VARIOUS SETTINGS)
• Correct the number of points in
the "RWw/RWr Setting" in the
"Network Configuration Settings"
of the master station.
• Check the firmware version of
the CPU module and the master
module. ( Page 46
Applicable products)
• Correct "Safety Communication
Setting" of the master station
again.
• When the parameter setting has
no errors, there may be an
influence from noise or a
hardware failure. If the same
error occurs again even after
measures have been taken
against noise, the module may
be in failure. Please consult your
local Mitsubishi representative.
• Check the network status using
the CC-Link IE Field Network
diagnostics of the engineering
tool for errors.
• When no error has occurred on
the network, there may be an
influence from noise or a
hardware failure. If the same
error occurs again even after
measures have been taken
against noise, the module may
be in failure. Please consult your
local Mitsubishi representative.