Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 142

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Error code
Safety error subset code
(hexadecimal)
Error
classification
*1
0204H
450
*1
0205H
450
0206H
450
10 TROUBLESHOOTING
140
10.7 List of Error Codes
Classification
Error item
number
(hexadecimal)
0204H
Minor error
Recoverable
0205H
Minor error
0206H
Minor error
Error name
Description and
cause
Double input
A double input
discrepancy
discrepancy was
detection error
detected in a pair of
inputs (X0 and X1,
X2 and X3, ...).
Input dark test
During an input dark
error
test, test pulses
were not detected.
I/O data error
An error was
detected in the I/O
data.
Action
• Match the ON timing of the
external power supply with the
ON timing of the module power
supply.
• Correct the parameter settings
of "Double input discrepancy
detection time".
• Review the connected devices
and wiring.
• When the connected devices
and wiring have no errors, there
may be an influence from noise
or a hardware failure. Take
measures to reduce noise.
• If the same error occurs again,
the module may be in failure.
Please consult your local
Mitsubishi representative.
• When "Double input discrepancy
auto recovery setting" is set to
"1: Used", the module will
recover from this error after the
double input discrepancy is
eliminated.
• Match the ON timing of the
external power supply with the
ON timing of the module power
supply.
• Correct the parameter settings
of "Input dark test pulse OFF
time" and "Number of pulse
output for input dark test".
• Review the connected devices
and wiring.
• When the connected devices
and wiring have no errors, there
may be an influence from noise
or a hardware failure. Take
measures to reduce noise.
• If the same error occurs again,
the module may be in failure.
Please consult your local
Mitsubishi representative.
• Match the ON timing of the
external power supply with the
ON timing of the module power
supply.
• Review the connected devices
and wiring.
• When the connected devices
and wiring have no errors, there
may be an influence from noise
or a hardware failure. Take
measures to reduce noise.
• If the same error occurs again,
the module may be in failure.
Please consult your local
Mitsubishi representative.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents