Error code
Safety error subset code
(hexadecimal)
Error
classification
0530H
450
0580H
450
0582H
450
0590H
450
0591H
450
Classification
Error item
number
(hexadecimal)
0530H
Moderate error
Recoverable
0580H
Moderate error
Recoverable
0582H
Moderate error
Recoverable
0590H
Moderate error
Recoverable
0591H
Moderate error
Recoverable
Error name
Description and
cause
Parameter data
An incorrect value
error (input dark
or parameter (input
test execution
dark test execution
setting)
setting) out of the
range is set.
Parameter data
An incorrect value
error (module
or parameter data
identification
(module
code)
identification code)
out of the range is
set.
Parameter data
An incorrect value
error (wiring
or parameter (wiring
selection of
selection of output)
output)
out of the range is
set.
Parameter data
An incorrect value
error (output
or parameter
dark test
(output dark test
execution
execution setting)
setting)
out of the range is
set.
Parameter data
An incorrect value
error (output
or parameter
dark test pulse
(output dark test
OFF time
pulse OFF time
setting)
setting) out of the
range is set.
Action
• Correct the module parameter
settings (input dark test
execution setting) and module
configuration.
• When "Wiring selection of input"
Xn (n: even number) is set to "1:
Double wiring (NC/NC)", set the
same value for Xn+1.
• When the parameters are set
again and the parameter setting
has succeeded, the module will
recover from this error.
• Correct the module parameter
setting and module
configuration.
• Check that the actual
configuration matches with the
module configuration set in the
"Network Configuration Settings"
of engineering tool.
• When the parameter is set again
and the parameter setting has
succeeded, the module will
recover from this error.
• Correct the module parameter
settings (wiring selection of
output) and module
configuration.
• When "Wiring selection of
output" Yn (n: even number) is
set to "1: Double wiring (Source/
Source)", set the same value for
Yn+1.
• When the parameters are set
again and the parameter setting
has succeeded, the module will
recover from this error.
• Correct the module parameter
settings (output dark test
execution setting) and module
configuration.
• When "Wiring selection of
output" Yn (n: even number) is
set to "1: Double wiring (Source/
Source)", set the same value for
Yn+1.
• When the parameters are set
again and the parameter setting
has succeeded, the module will
recover from this error.
• Correct the module parameter
settings (output dark test pulse
OFF time setting) and module
configuration.
• When "Wiring selection of
output" Yn (n: even number) is
set to "1: Double wiring (Source/
Source)", set the same value for
Yn+1.
• When the parameters are set
again and the parameter setting
has succeeded, the module will
recover from this error.
10 TROUBLESHOOTING
143