Error code
Classification
(hexadecimal)
*1
0580H
Moderate error
Recoverable
*1
0582H
Moderate error
Recoverable
*1
0590H
Moderate error
Recoverable
*1
0591H
Moderate error
Recoverable
*1
05F0H
Moderate error
Recoverable
*1 Detailed information of the error is stored in Error code details in Error history data. For Error code details, refer to the following.
Page 151 Error code details (NZ2GFSS2-8D-S1, NZ2GFSS2-8TE-S1, NZ2GFSS2-16DTE-S1)
*2 If power-off of the module power supply coincides with the safety diagnostics, an error of the hardware failure can be logged in the error
history. Restart the module and check that the error has been eliminated before using the module.
When multiple errors have occurred, only the latest error code is stored in Error code. The errors that occurred
before can be checked by executing "Error history read" of the "Network Configuration Settings" in the
engineering tool. For the error history, refer to the following.
Page 132 How to Check Error Codes
However, when a moderate error occurs during a major error occurrence, the error code of the major error will
remain in Error code.
10 TROUBLESHOOTING
148
10.7 List of Error Codes
Error name
Description and cause
Parameter data
A value with an error or
error (module
parameter data (module
identification code)
identification code) out of the
range is set.
Parameter data
A value with an error or
error (wiring
parameter (wiring selection of
selection of output)
output) out of the range is set.
Parameter data
A value with an error or
error (output dark
parameter (output dark test
test execution
execution setting) out of the
setting)
range is set.
Parameter data
A value with an error or
error (output dark
parameter (output dark test
test pulse OFF time
pulse OFF time setting) out of
setting)
the range is set.
Parameter data
A value with an error or
error (extension
parameter out of the range is
module)
set.
Action
• Correct the module parameter setting and module
configuration.
• Check that the actual configuration matches with the
module configuration set in the "Network Configuration
Settings" of engineering tool.
• When the parameter is set again and the parameter setting
has succeeded, the module will recover from this error.
• Correct the module parameter settings (wiring selection of
output) and module configuration.
• When "Wiring selection of output" Yn (n: even number) is
set to "1: Double wiring (Source/Source)", set the same
value for Yn+1.
• When the parameters are set again and the parameter
setting has succeeded, the module will recover from this
error.
• Correct the module parameter settings (output dark test
execution setting) and module configuration.
• When "Wiring selection of output" Yn (n: even number) is
set to "1: Double wiring (Source/Source)", set the same
value for Yn+1.
• When the parameters are set again and the parameter
setting has succeeded, the module will recover from this
error.
• Correct the module parameter settings (output dark test
pulse OFF time setting) and module configuration.
• When "Wiring selection of output" Yn (n: even number) is
set to "1: Double wiring (Source/Source)", set the same
value for Yn+1.
• When the parameters are set again and the parameter
setting has succeeded, the module will recover from this
error.
• Correct module parameter settings of the extension module
and module configuration.
• When the parameters are set again and the parameter
setting has succeeded, the module will recover from this
error.