Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 195

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

Module control data area
These areas are used for controlling the module data of the safety remote I/O module.
■Error history clear command
This area is used to clear error history stored in the module.
Address
Name
(hexadecimal)
1000H
Error history clear command
• Clear operation of error history
When Error history clear command (address: 1000H) is set to Commanded (1), the error history is cleared.
Stored condition of an error history
Error history clear command
(address: 1000H)
Error history clear completed
(address: 1001H)
Controlled by the safety remote I/O module
Controlled by the program
Error history clear command cannot be used to clear an error code of Warning status flag (RX) and Error
status flag (RX).
■Error history clear completed
This area indicates whether the clear operation of error history stored in the module is completed or not.
Address
Name
(hexadecimal)
1001H
Error history clear completed
• Clear operation of error history
When the clear operation of the error history is completed, Error history clear completed (address: 1001H) is turned to
Completed (1). For the timing where the area is turned to Not performed (0)  Completed (1)  Not performed (0), refer to
the following.
Page 193 Error history clear command
An error history is stored.
Not
Commanded (1)
commanded (0)
Not performed (0)
Setting range
0: Not commanded
1: Commanded
An error history is not stored.
Not
commanded (0)
Completed
Not
(1)
performed (0)
Setting range
0: Not performed
1: Completed
Appendix 4 Remote Buffer Memory
Default value
0
A
Default value
0
APPX
193