8.2

Safety Output Function

This function safely outputs signals. This function cannot be used in any modes other than the safety operation mode. All the
safety remote outputs (SA\Y) are off in any modes other than the safety operation mode.

Safety output wiring selection function

This function is used to select double wiring or single wiring of the output wiring.
Double wiring function
The double wiring function supports double outputs. By multiplying output signals using double wiring, safety outputs can be
turned off even though one of the signals has an error.
IO24V
External power supply
IO24G
■Combination for double wiring
Use the following combinations of output terminals for double wiring to the safety remote I/O module.
Combination of output terminals
Y0, Y1
The following table lists the relation of output terminals (Y) and safety remote outputs (SA\Y).
Safety remote output (SA\Y)
SA\Y0
SA\Y1
SA\Y6
SA\Y7
Y0
Y1
Safety remote I/O module
COM-
Y2, Y3
MC
Load
MC
Load
Y4, Y5
Output terminal (Y)
Y0
Y1
Y6
Y7
Y6, Y7
8 FUNCTIONS
8.2 Safety Output Function
8
89