Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 147

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

■NZ2GFSS2-8D-S1, NZ2GFSS2-8TE-S1, NZ2GFSS2-16DTE-S1
Error code
Classification
(hexadecimal)
0001H
Major error
0101H
Moderate error
*1
0102H
Moderate error
*1
0103H
Moderate error
0104H
Moderate error
*1
0105H
Moderate error
0106H
Moderate error
0107H
Moderate error
0108H
Moderate error
*1
0109H
Moderate error
Error name
Description and cause
Hardware failure
A hardware failure was
detected.
Self-diagnostic error
An error was detected by the
self-diagnostics.
External power
An external power supply
supply voltage error
error was detected.
Module
The module configuration has
configuration
been changed after power on.
changed
Date out of range
Incorrect clock data was
error
received from the CPU
module.
Improper module
A module that cannot be used
connected
for extension is connected.
Restart not
The module has not been
performed after
restarted after the safety
safety module
module validation.
validation
Non-volatile
An error of the parameter data
memory data error
stored in the non-volatile
(parameter)
memory has been detected.
Non-volatile
An error of the control data
memory data error
stored in the non-volatile
(control data)
memory has been detected.
Output read-back
A discrepancy of an output
error
read-back value and an output
value was detected.
Action
There may be an influence from noise or a hardware failure. If
the same error occurs again even after measures have been
taken against noise, the module may be in failure. Please
consult your local Mitsubishi representative.
• Match the ON timing of the external power supply with the
ON timing of the module power supply.
• Review the connected devices, wiring, and voltage.
• There may be an influence from noise of external wiring
(such as power supply part and I/O signal part). Take
measures to reduce noise.
• If the same error occurs again, the module may be in
failure. Please consult your local Mitsubishi representative.
• Check the connection status of the extension module.
• If the module is connected properly, there may be an
influence from noise or a hardware failure. If the same error
occurs again even after measures have been taken against
noise, the module may be in failure. Please consult your
local Mitsubishi representative.
There may be an influence from noise or a hardware failure. If
the same error occurs again even after measures have been
taken against noise, the module may be in failure. Please
consult your local Mitsubishi representative.
Check whether the extension module connected is
connectable to this product. If the module is connectable,
there may be an influence from noise or a hardware failure. If
the same error occurs again even after measures have been
taken against noise, the module may be in failure. Please
consult your local Mitsubishi representative.
• Restart the module.
• If the same error occurs again, the module may be in
failure. Please consult your local Mitsubishi representative.
• The module will recover from this error by initializing
parameters by using Parameter area initialization
command. In such a case, parameters are required to be
set again by users.
• If the same error occurs again, the module may be in
failure. Please consult your local Mitsubishi representative.
• Check parameters again and perform the safety module
validation.
• If the same error occurs again, the module may be in
failure. Please consult your local Mitsubishi representative.
• Match the ON timing of the external power supply with the
ON timing of the module power supply.
• Review the connected devices and wiring.
• Check that 24V is supplied to the external power supply
using a tester.
• Check that the external connection is not overloaded.
• When the connected devices and wiring have no errors,
there may be an influence from noise or a hardware failure.
Take measures to reduce noise.
• If the same error occurs again, the module may be in
failure. Please consult your local Mitsubishi representative.
10 TROUBLESHOOTING
10.7 List of Error Codes
10
*2
145

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents