Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 189

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

■Double input discrepancy detection type
Set the detection type of the double input discrepancy.
Address
Name
(hexadecimal)
0131H
Double input discrepancy detection type
b15
b14
b13
b12
0 (fixed)
The following describes the setting range of the parameter.
• Discrepancy detection time specified: The discrepancy detection time setting is required in the "Double input discrepancy
detection time" parameter.
• Discrepancy detection time not specified: The discrepancy detection time setting is not required in the "Double input
discrepancy detection time" parameter. The double input discrepancy is detected not by the elapsed time after the
discrepancy has occurred, but after the double input status turns on from the discrepancy state and remains on for 500ms.
When "0: Not used" or "2: Single wiring" is selected in the wiring selection of input, or "1: Do not detect" is
selected in the double input discrepancy detection setting, this parameter will be ignored.
■Double input discrepancy auto recovery setting
Set whether to use or not the auto recovery at double input discrepancy detection error.
Address
Name
(hexadecimal)
0132H
Double input discrepancy auto recovery setting
When "0: Not used" or "2: Single wiring" is selected in the wiring selection of input for all points, or "0: Do not
detect" is selected in the double input discrepancy detection setting for all points, the double input discrepancy
detection error does not occur and the automatic recovery is not performed.
■Double input discrepancy detection time
Set the double input discrepancy detection time.
Address
Name
(hexadecimal)
0140H to 0143H
Double input discrepancy detection time
When "0: Not used" or "2: Single wiring" is selected in the wiring selection of input, "1: Do not detect" is
selected in the double input discrepancy detection setting, or "1: Discrepancy detection time not specified" is
selected in the double input discrepancy detection type, this parameter will be ignored.
b11
b10
b9
b8
Setting range
0: Discrepancy detection time specified
1: Discrepancy detection time not specified
b7
b6
b5
b4
Setting range
0: Not used
1: Used
Setting range
1 to 6000 (10ms)
Appendix 4 Remote Buffer Memory
Default value
0000H
b3
b2
b1
b0
X6
X4
X2
X0
X7
X5
X3
X1
Default value
0000H
Default value
1 (10ms)
APPX
187
A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents