Mitsubishi Electric NZ2GFSS2 32D S1 User Manual page 77

Programmable controller cc-link ie field network remote i/o module with safety functions
Table of Contents

Advertisement

■NZ2GFSS2-8TE-S1
Unit
Item
Station parameter
Safety setting
I/O LED indication setting at error occurrence
Cyclic data update monitoring time setting
Extension I/O setting
Operation setting of external power supply voltage error detection
Basic module
Wiring selection of output
parameter_main
module
Output dark test execution
setting
Output dark test pulse OFF
time setting
Number of pulse output for
output dark test
Number of ON times
integration function enable
Transmission interval monitoring
time
Input response time setting
Output HOLD/CLEAR setting
Wiring selection of output Y0 to
Wiring selection of output Y7
Output dark test execution setting
Y0 to Output dark test execution
setting Y7
Output dark test pulse OFF time
setting Y0 to Output dark test pulse
OFF time setting Y7
Number of pulse output for output
dark test Y0 to Number of pulse
output for output dark test Y7
Number of ON times integration
function enable Y0 to Number of ON
times integration function enable Y7
Setting range
Reference
4 to 1000ms (default: 35)
Page 37 Safety remote I/O
module safety response time
0: No indication of error point
(default)
1: Indication of error point
0 to 20 (default: 0)  100ms
0: 0ms
1: 0.2ms
2: 1.0ms
3: 1.5ms
4: 5ms
5: 10ms (default)
6: 20ms
7: 70ms
0: CLEAR (default)
1: HOLD
0: Stop safety communication
Page 110 Operation Setting
(default)
Function at Detection of
1: Continue safety
External Power Supply
communication (Without output
Voltage Error
interlock)
2: Continue safety
communication (With output
interlock)
0: Not used (default)
Page 89 Safety output wiring
1: Double wiring (Source/Source)
selection function
2: Single wiring
0: Perform (default)
Page 105 Output dark test
1: Do not perform
function
0: 400s (default)
1: 1ms
2: 2ms
0: 1 time (default)
1: 2 times
2: 3 times
0: Disable (default)
Page 92 Number of safety
1: Enable
output ON times integration
function
7 VARIOUS SETTINGS
7.2 Parameter Settings
7
75

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents