Error code
Safety error subset code
(hexadecimal)
Error
classification
*1
0207H
450
*1
0208H
450
020AH
450
Classification
Error item
number
(hexadecimal)
0207H
Minor error
0208H
Minor error
020AH
Minor error
Recoverable
Error name
Description and
cause
Output read-
A discrepancy of an
back error
output read-back
value and an output
value was detected.
Output dark test
During an output
error
dark test, test
pulses were not
detected.
Safety module
The safety module
validation failure
validation failed.
Action
• Match the ON timing of the
external power supply with the
ON timing of the module power
supply.
• Review the connected devices
and wiring.
• Check that 24V is supplied to the
external power supply using a
tester.
• Check that the external
connection is not overloaded.
• When the connected devices
and wiring have no errors, there
may be an influence from noise
or a hardware failure. Take
measures to reduce noise.
• If the same error occurs again,
the module may be in failure.
Please consult your local
Mitsubishi representative.
• Match the ON timing of the
external power supply with the
ON timing of the module power
supply.
• Correct the parameter settings
of "Output dark test pulse OFF
time" and "Number of pulse
output for output dark test".
• Review the connected devices
and wiring.
• Check that 24V is supplied to the
external power supply using a
tester.
• Check that the external
connection is not overloaded.
• When the connected devices
and wiring have no errors, there
may be an influence from noise
or a hardware failure. Take
measures to reduce noise.
• If the same error occurs again,
the module may be in failure.
Please consult your local
Mitsubishi representative.
• Check that no error other than
"Safety module validation
failure" has occurred on the
module using the ERR. LED of
the module and error history. If
an error has occurred, eliminate
the cause.
• If the same error occurs again
even after "Safety module
validation" is executed in no
error state, the module may be
in failure. Please consult your
local Mitsubishi representative.