Wiring of terminal block for the external power supply and I/O
signals
Tightening torque
Tighten the terminal block mounting screws within the following specified torque range. Tightening the screws too much may
damage the module case.
Screw type
Terminal block mounting screw (M2 screw)
Wire to be used
The following table describes the wire to be connected to the terminal block for the external power supply and I/O signals.
When using the safety remote I/O module as a UL listed product, use the following wires.
Diameter
Type
22 to 16 AWG
Stranded wire
Installing and removing the terminal block
■Removal procedure
Terminal block
mounting screw
Tightening torque range
0.1 to 0.2Nm
Material
Temperature rating
Copper wire
75 or higher
1.
Loosen the terminal block mounting screws.
2.
When the terminal block mounting screws are loosened,
the terminal block can be removed.
Stripping length of the cable
10mm
6 INSTALLATION AND WIRING
6.4 Wiring
6
63