Processing method of the cable terminal
• When using a stranded wire, strip the cable 10mm from the tip. Stripping the cable too long may cause electric shock or
short circuit between adjacent terminals because the conductive part sticks out of the terminal block. Stripping the cable too
short may cause a poor contact to the spring clamp terminal part.
• When using a bar solderless terminal, follow the specifications of the bar solderless terminal for how long the cable should
be stripped. To attach a bar solderless terminal to a wire, use a crimping tool.
List of bar solderless terminals
When using a bar solderless terminal, the products listed below are recommended. For a processing method of the cable
terminal, such as the stripping length of the cable, follow the specifications of the terminal used. Use UL listed bar solderless
terminals, and for processing, use a tool recommended by manufacturers of solderless terminals.
Terminal shape
Ferrule (with insulation sleeve)
Ferrule (without insulation sleeve)
*1 When using the safety remote I/O module as a UL listed product, use the terminals whose model name ends with -10 or -10.
*1
Model
Applicable wire size
AI 0.34-10TQ
0.34 (22 AWG)
AI 0.5-10WH
0.5 (20 AWG)
AI 0.75-10GY
0.75 (18 AWG)
A 1-10
1.0 (18 AWG)
A 1.5-10
1.5 (16 AWG)
Bar solderless terminal tool Contact
CRIMPFOX6
6 INSTALLATION AND WIRING
PHOENIX CONTACT GmbH & Co. KG
6.4 Wiring