Nortel DMS 100 Series Maintenance Manual page 251

Remote switching center multi-access
Hide thumbs Also See for DMS 100 Series:
Table of Contents

Advertisement

Note 1: Perform this step for each link ManB.
Note 2: To test the other links associated with the RCO2, execute the
procedures in this step for each link. Continue until all links are tested.
If the test of the link(s)
passed
failed
22
To return to service (RTS) the links, type
>RTS link_number
and press the Enter key.
where
Note: To RTS the other links associated with the RCO2, execute the
procedures in this step for each link. Continue until all links are RTS.
If RTS
passed on all links
failed
23
Go to the common returning a card procedure in this document.
24
You have completed this procedure. Remove the sign from the active unit.
Return to the maintenance procedure that directed you to this card
replacement procedure. Continue as directed.
25
Contact the personnel responsible for higher level support for additional help
to replace this card.
DMS-100 Family Remote Switching Center Multi-Access Maintenance Manual XPM11 and up
link_no
is the number of the link ManB in step 11
link_number
is the number of the link tested in step 21
RSC-M card replacement procedures
in an RSC-M
Do
step 22
step 25
Do
step 23
step 25
6-99
NTMX87
(end)