Nortel DMS 100 Series Maintenance Manual page 208

Remote switching center multi-access
Hide thumbs Also See for DMS 100 Series:
Table of Contents

Advertisement

6-56 RSC-M card replacement procedures
NTMX75
in an RSC-M
(end)
15
At the MAP terminal
16
17
18
19
20
21
297-8223-550 Standard 04.02 November 2000
If
a maintenance procedure does not direct you to this
procedure
Remove the sign from the active unit. Return to the maintenance procedure
that sends you to this procedure. Continue as directed.
To return the inactive unit to service, type:
>RTS
INACTIVE
and press the Enter key.
If the RTS command
passes
fails
Remove the sign from the active unit.
Go to the common returning a card procedure in this document.
The procedure is complete.
For additional help, contact the next level of maintenance.
For additional help with SWACT, contact the next level of maintenance.
Note: The system can recommend that you use the SWACT command
with the FORCE option. Consult office personnel to determine if you must
use the FORCE option.
Do
step 16
Do
step 17
step 20