6-66 RSC-M card replacement procedures
NTMX77
in an RSC-M
(continued)
To replace an NTMX77 in an RSC-M
At the MAP display
1
2
At the MAP terminal
3
297-8223-550 Standard 04.02 November 2000
Proceed only if one of the following conditions apply. The maintenance
support group or a step in a maintenance procedure directs you to this card
replacement procedure. Use the procedure to verify or accept cards.
WARNING
Loss of service
To replace a card in the RSC-M, make sure the unit in which
you replace the card is inactive and the mate unit is active.
Obtain an NTMX77 replacement circuit card. Make sure the replacement
circuit card contains the same product engineering code (PEC) and suffix as
the circuit card that you remove.
Make sure the current MAP display is at the peripheral module (PM) level. To
post the RSC-M/RCO2, type
>MAPCI;MTC;PM;POST RCO2 rco2_no
and press the Enter key.
where
rco2_no
is the number of the RCO2 that you post.
Example of a MAP response:
RCO2
SysB
0 Quit
PM
0
2 Post_
RCO2
0
3 ListSet
4
RCO2
0 ISTb
5 TRNSL
Unit0:
6 TST
Unit1:
7 BSY
8 RTS
9 OffL
10 LoadPM_
11 Disp_
12 Next_
13 SwAct
14 QueryPM
15
16 IRLINK
17 Perform
18
ManB
OffL
0
2
0
0
Links_OOS:
CSide
Inact ISTb
Act InSv
CBsy
ISTb
InSv
0
2
25
0
1
1, PSide
1
1

Advertisement

Table of Contents
loading

Table of Contents