Nortel DMS 100 Series Maintenance Manual page 180

Remote switching center multi-access
Hide thumbs Also See for DMS 100 Series:
Table of Contents

Advertisement

6-28 RSC-M card replacement procedures
NTMX72
in an RSC-M
(continued)
To replace an NTMX72 in an RSC-M
At the MAP display
1
2
At the MAP terminal
3
297-8223-550 Standard 04.02 November 2000
Proceed if one of the following conditions apply:
a step in a maintenance procedure directed you to this card replacement
procedure
you use this procedure to verify or accept cards
the maintenance support group directed you to this procedure.
WARNING
Loss of service
When you replace a card in the RSC-M, make sure the unit in
which you replace the card is inactive and the mate unit is
active.
Obtain an NTMX72 replacement circuit card. Make sure the replacement
circuit card has the same product engineering code (PEC) and PEC suffix, as
the circuit card to be removed.
To access the peripheral module (PM) level of the MAP display and to post
the RSC-M/RCO2 with the defective card, type:
>MAPCI;MTC;PM;POST RCO2 rco2_no
and press the Enter key.
where
rco2_no
is the PM number zero to 255
Example of a MAP response: