3.6

Control I/O Connections

This section gives information about the settings for the listed control circuit I/O signals.
• MFDI (terminals DI1 to DI7)
• Pulse train output (terminal PO)
• MFAI (terminal AI2)
• MFAO (terminal AO)
• Modbus communications (terminals RS485+, RS485-, A0V)

Set Sinking Mode/Sourcing Mode

Close the circuit between terminals DIC-D24V and DIC-D0V to set the sinking mode/sourcing mode and the
internal/external power supply for the MFDI terminals. The default setting for the drive is internal power supply
sinking mode.
NOTICE: Do not close the circuit between terminals D24V and D0V. A closed circuit between these terminals will cause
damage to the drive.
Mode
Internal Power Supply (Terminal D0V-D24V)
Sinking Mode
(NPN)
Sourcing Mode
(PNP)

Pulse Train Output

You can use pulse train monitor output terminal PO for sourcing mode or for sinking mode.
• Use for sourcing mode
The load impedance changes the voltage level of the pulse train output signal.
Load Impedance
Note:
Use the formula below to calculate the necessary load resistance (kΩ) to increase output voltage V
SIEPCYEUOQ2V01A Q2V Technical Manual
R
(kΩ)
L
1.5 kΩ or more
4.0 kΩ or more
10 kΩ or more

3.6 Control I/O Connections

External 24 V power supply
Output Voltage
V
(V)
PO
5 V or more
8 V or more
10 V or more
(V).