B2: Dc Inj / Short Ckt Brake; B3: Speed Search - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

No.
Name
(Hex.)
b1-16
Run Comm. Sel 2
(01C5)
b1-17
RUN@PowerUp
Selection
(01C6)
b1-35
DI Deadband Time
(1117)
Expert

b2: DC INJ / SHORT CKT BRAKE

No.
Name
(Hex.)
b2-01
ZSpd/DCI Threshold
(0189)
b2-02
DCI Braking Current
(018A)
b2-03
DCInj Time@Start
(018B)
b2-04
DCInj Time@Stop
(018C)
b2-08
MagFlux Comp Value
(0190)
b2-12
SCB Time@Start
(01BA)
b2-13
SCB Time@Stop
(01BB)
b2-18
SCB Current
(0177)

b3: SPEED SEARCH

No.
Name
(Hex.)
b3-01
SpSrch@Start Selection
(0191)
b3-02
SpSrch Deactivation
Current
(0192)
SIEPCYEUOQ2V01A Q2V Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input method for Run Command 2 when the user switches the control circuit
terminals ON/OFF to change the Run command source.
0 : Keypad
1 : Analog Input
2 : Modbus
3 : Option PCB
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets drive response when energizing a drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run
command.
1 : Disregard RUN
2 : Accept RUN
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the deadband time for MFDIs.
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency to start DC Injection Braking or Short Circuit Braking.
Note:
This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp-
>Stop].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the DC Injection Braking current as a percentage of the drive rated current.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the DC Injection Braking Time at stop.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the DC Injection Braking Time at stop.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets how much current the drive injects when DC Injection Braking at Start starts
(Initial Excitation) as a percentage of E2-03 [Mot No-Load Current].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking time at start.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Short Circuit Braking time at stop.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Short Circuit Braking Current as a percentage of the motor rated current.
Note:
Parameter A1-02 [Control Method] selects which parameter is the motor rated
current.
• A1-02 = 5, 6 [PM OLVector, PM AOLVector]: E5-03 [PM Mot Rated Current
(FLA)]
• A1-02 = 8 [EZ Vector]: E9-06 [Motor Rated Current]
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Speed Search at Start function where the drive will perform Speed Search with
each Run command.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the current level that stops Speed Search as a percentage of the drive rated output
current. Usually it is not necessary to change this setting.
11.4 b: APPLICATION
Default
Ref.
(Setting Range)
0
452
(0 - 3)
1
453
(1, 2)
0.0 ms
453
(0.0 to 100.0 ms)
Default
Ref.
(Range)
Determined by A1-02
454
(0.0 - 10.0 Hz)
50%
454
(0 - 75%)
0.00 s
455
(0.00 - 10.00 s)
Determined by A1-02
455
(0.00 - 10.00 s)
0%
455
(0 - 1000%)
0.00 s
456
(0.00 - 25.50 s)
A1-02 = 8: 0.00 s
456
Other than A1-02 = 8:
0.50 s
(0.00 - 25.50 s)
100.0%
456
(0.0 - 200.0%)
Default
Ref.
(Range)
Determined by A1-02
460
(0, 1)
Determined by A1-02
460
(0 - 200%)
319
11