11.11 n: SPECIAL
No.
Name
(Hex.)
HFI LPF Cutoff Frq
n8-39
(0566)
HFI PoleDet Pgain
n8-41
(0568)
Expert
HFI PoleDet iTime
n8-42
(0569)
Expert
SpdFbck Det.Gain
n8-45
(0538)
Pull-In Comp.Time
n8-47
Constant
(053A)
Pull-In Current (for PM
n8-48
Motors)
(053B)
RUN
Heavy Load Id Current
n8-49
(053C)
RUN
Expert
Medium Load Iq Level
n8-50
(High)
(053D)
Expert
Ac/Dec Pull-In Current
n8-51
(053E)
Volt-Err Compensation
n8-54
Time
(056D)
Expert
Load Inertia
n8-55
(056E)
High-Freq Injection
n8-57
(0574)
Output Volt Limit Level
n8-62
(057D)
Expert
Output Voltage Limit P
n8-63
Gain
(057E)
Expert
SpdFbk Gain@OV
n8-65
Suppression
(065C)
Expert
Spd Obs. P Gain Control
n8-69
(065D)
Expert
378
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the low-pass filter shut-off frequency for high frequency injection.
Note:
• Set n8-35 = 2 [InitRotorPos Selection = HiFreq Injection] or n8-57 = 1 [High-
Freq Injection = Enabled] to enable this parameter.
• The drive automatically calculates this value when High Frequency Injection
Auto-Tuning completes successfully.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the response gain for the high frequency injection speed estimation.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the integral time constant for the high frequency injection speed estimation.
Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the internal speed feedback detection reduction unit gain as a magnification value.
Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the time constant the drive uses to align the pull-in current reference value with the
actual current value. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
On the basis that parameter E5-03 [PM Mot Rated Current (FLA)] is the 100% value,
this parameter sets the d-axis current that flows to the motor during run at constant
speed as a percentage.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the d-axis current to that the drive will supply to the motor to run it at a constant
speed with a heavy load. Considers E5-03 [PM Mot Rated Current (FLA)] to be 100%.
Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the load current level at which heavy load control starts where E5-03 [PM Mot
Rated Current (FLA)] is 100%. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the pull-in current allowed to flow during acceleration/deceleration as a percentage
of the motor rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5 [PM OLVector]: E5-03 [PM Mot Rated Current (FLA)]
• A1-02 = 8 [EZ Vector]: E9-06 [Motor Rated Current]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time constant that the drive uses when adjusting for voltage errors.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the ratio between motor inertia and machine inertia.
1 : <1:10
2 : 1:10-1:30
3 : 1:30-1:50
4 : >1:50
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that detects motor speed with high frequency injection.
Note:
When you set n8-57 = 1, doHigh Frequency Injection Auto-Tuning.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the output voltage limit to prevent saturation of the output voltage. Usually it is not
necessary to change this parameter.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the proportional gain for output voltage control. Usually it is not necessary to
change this setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain of internal speed feedback detection suppression while the overvoltage
suppression function is operating as a magnification value. Usually it is not necessary to
change this parameter.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Usually it is not necessary to change this setting. Sets the Proportional gain that the
drive uses for speed estimation.
Default
(Range)
250 Hz
(0 - 1000 Hz)
2.5
(-10.0 - +10.0)
0.10 s
(0.00 - 9.99 s)
0.80
(0.00 - 10.00)
5.0 s
(0.0 - 100.0 s)
30%
(0 - 200%)
Determined by E5-01
(-200.0 - +200.0%)
80%
(50 - 255)
Determined by A1-02
(0 - 200%)
1.00 s
(0.00 - 10.00 s)
1
(1 - 4)
0
(0, 1)
200 V Class: 200.0 V,
400 V: 400.0 V
(200 V Class: 0.0 to
230.0 V, 400 V Class:
0.0 to 460.0 V)
1.00
(0.00 - 100.00)
1.50
(0.00 - 10.00)
1.00
(0.00 - 20.00)
SIEPCYEUOQ2V01A Q2V Technical Manual
Ref.
686
686
687
687
687
687
688
688
688
688
688
689
689
690
690
690