O2: Keypad Operation - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

o1-58: Mot Capacity Unit
No.
Name
(Hex.)
Mot Capacity Unit
o1-58
(3125)
The drive shows these parameter values in the set units:
• E2-11 [Motor Rated Power (kW)]
• E4-11 [M2 Rated Power (kW)]
• E5-02 [PM Mot Rated Power (kW)]
• E9-07 [Motor Rated Power (kW)]
• T1-02 [Motor Rated Power]
• T2-04 [PMMot Rated Power]
• T4-08 [Motor Rated Capacity]
0 : kW
Shows the motor output in kW units.
1 : HP
Shows the motor output in HP units.

o2: KEYPAD OPERATION

o2-01: LO/RE Key Selection of Function
No.
Name
(Hex.)
LO/RE Key Selection of
o2-01
Function
(0505)
0 : Disabled
You cannot use
to switch between LOCAL and REMOTE Modes.
1 : Enabled
You can use
to switch between LOCAL and REMOTE Modes when the drive is stopped. When LOCAL
Mode is selected,
WARNING! Sudden Movement Hazard. If you change the control source when b1-07 = 2 [LO/RE Run Selection = Accept RUN],
the drive can start suddenly. Before you change the control source, remove all personnel from the area around the drive, motor,
and load. Sudden starts can cause serious injury or death.
WARNING! Sudden Movement Hazard. Fully examine all mechanical and electrical connections before you change o2-01 [LO/
RE Key Selection of Function] or b1-07 [LO/RE Run Selection]. Sudden starts can cause serious injury or death. If b1-07 = 2
[LO/RE Run Selection = Accept RUN] and there is an active Run command when you switch from LOCAL to REMOTE Mode,
the drive can start suddenly.
Function Selection
o2-01 = 0 [Disabled]
o2-01 = 1 [Enabled]
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the setting unit for parameters that set the motor rated power.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that lets you use
on the keypad will come on.
Table 12.56 Function Settings with o2-01 and b1-07
LOCAL/REMOTE Run Selection
b1-07 = 1 [Cycle RUN]
b1-07 = 2 [Accept RUN]
b1-07 = 1 [Cycle RUN]
b1-07 = 2 [Accept RUN]
Description
Description
to switch between LOCAL and REMOTE Modes.
Switching from LOCAL Mode to
REMOTE Mode
The drive will not switch modes.
The drive will not start operating although
the Run command is active. When you set
Run command to active again, the drive
will start to run.
When the Run command is active, the
drive will start to run immediately when
the mode switches from LOCAL to
REMOTE.
12.10 o: KEYPAD
Default
(Range)
0
(0, 1)
Default
(Range)
1
(0, 1)
Switching from REMOTE Mode to
LOCAL Mode
The drive will not switch modes.
The drive cannot operate because the Run
command is not enabled.
The drive cannot operate because the Run
command is not enabled.
701