• The controller and card communicate in the format of
each field bus communications protocol.
• Drive 0 sends commands and monitors through normal
field bus communications.
• The special registers of Drive 0 use read and write to
send commands to and monitor Drives 1 to 4.
Operations at the Time of Communication Error
Error
Communication Error
Codes
From controller to
bUS
communication option
From communication
oFAxx
option to master drive
From master drive to
CE
slave drive
Gateway Special Register Specification
Register
No. (Hex.)
Command source update
bit 0
Drive 1 Update Command Enabled
bit 1
Drive 2 Update Command Enabled
15C5
bit 2
Drive 3 Update Command Enabled
bit 3
Drive 4 Update Command Enabled
bit 4
Update Register Access Command Enabled
bit 5 - F Reserved
Run Command (Drive 1)
H5-12 = 0: FWD/Stop
0 = Stop
1 = Forward run
bit 0
H5-12 = 1: Run/Stop
0 = Stop
1 = Run
H5-12 = 0: REV/Stop
0 = Stop
1 = Reverse run
15C6
bit 1
H5-12 = 1: FWD/REV
0 = Forward run
1 = Reverse run
bit 2
External fault
bit 3
Fault Reset
bit 4
ComRef
bit 5
ComCtrl
bit 6 - F Reserved
15C7
Frequency Reference (Drive 1)
SIEPCYEUOQ2V01A Q2V Technical Manual
Table 12.34 Operation in Gateway Mode
Communication Option to Master Drive (Drive 0)
Field bus communication data is written to and read from
the special registers of Drive 0.
• Master drive
Detects bUS [Option Communication Error] and operates as specified by F6-01 [Comm.Error Selection].
• Slave drive
Detects CE [Modbus Communication Error] and operates as specified by H5-04 [Mbus Error Stop].
Note:
• After error detection, each drive can continue the operation specified by the last received command if the F6-01 and H5-04 settings
agree. Because the controller cannot stop the operation, you must supply a stopping method, for example an emergency stop
switch.
• If you set H5-05 = 0 [Mbus Fault Detection Selection = Disabled], the drive will not detect CE. The H5-04 setting does not have
an effect.
• Master drive
Detects oFAxx and coasts to stop.
• Slave drive
Detects hLCE [High Level Communication Errors] and coasts to stop.
The master drive stops communicating with the slave drive in these conditions: Reset the fault to restart communication.
The slave drive detects CE after H5-09 [Mbus CE Detect Time] is expired. Then it operates in as specified with H5-04 [Mbus Error
Stop].
• A message error occurred in the send data from the slave drive 10 consecutive times.
• Response from the slave drive timed out 10 consecutive times.
Table 12.35 Command Data
Master Drive (Drive 0) to Slave Drives (Drives 1 to
• Uses Modbus communications.
• Drive 0 sends data from its special registers to Drives
1 to 4.
Operation
Description
This flag enables command updates.
To input the Run command and frequency reference at the same time, write all
commands, then change the bit value from 0 to 1.
The unit of measure changes when o1-03 changes.
12.6 F: OPTIONS
4)
12
549