Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

3.3 Main Circuit Wiring
Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2042
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2056
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2070
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2082
-, +1, +2
B1, B2
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
54
Recommended Gauge
Applicable Gauge
mm
2
10
2.5 - 16
10
2.5 - 16
16
4 - 25
4
2.5 - 6
10
6 - 16
16
4 - 25
16
4 - 25
25
6 - 35
10
4 - 16
10
10 - 25
25
6 - 35
16
6 - 25
35
10 - 50
10
4 - 16
16
10 - 25
35
10 - 50
25
10 - 35
50
16 - 70
16
4 - 16
16
10 - 25
Wire Stripping
*1
Length
mm
2
mm
10
10
18
10
-
18
18
18
10
-
20
20
20
10
-
20
20
20
10
-
Tightening Torque
Terminal Screw
N∙m (in∙lb)
1.5 - 1.7
M4
(13.5 - 15)
1.5 - 1.7
M4
(13.5 - 15)
2.3 - 2.5
M5
(19.8 - 22)
1.5 - 1.7
M4
(13.5 - 15)
2.0 - 2.5
M5
(17.7 - 22.1)
2.3 - 2.5
M5
(19.8 - 22)
2.3 - 2.5
M5
(19.8 - 22)
• ≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
M5
• 35 mm
2
4.1 - 4.5
(36 - 40)
1.5 - 1.7
M4
(13.5 - 15)
5.4 - 6.0
M6
(47.8 - 53.1)
5 - 5.5
M6
(45 - 49)
5 - 5.5
M6
(45 - 49)
5 - 5.5
M6
(45 - 49)
1.5 - 1.7
M4
(13.5 - 15)
5.4 - 6.0
M6
(47.8 - 53.1)
5 - 5.5
M6
(45 - 49)
5 - 5.5
M6
(45 - 49)
5 - 5.5
M6
(45 - 49)
1.5 - 1.7
M4
(13.5 - 15)
5.4 - 6.0
M6
(47.8 - 53.1)
2
(copper wire).