5.6 Safe Disable Input

5.6

Safe Disable Input

This section gives precautions to support the Safe Disable input. Contact the manufacturer for more information.
The TUV mark identifies that the product complies with the safety standards.
The safety function complies with the following standards.
Safety Standards
IEC/EN 61508:2010 (SIL3)
IEC 62061:2005/AMD2:2015 (SILCL3)
Functional Safety
EN 62061:2005/A2:2015 (SILCL3)
IEC 61800-5-2:2016 (SIL3)
EN 61800-5-2:2017 (SIL3)
ISO/EN ISO 13849-1:2015 (Cat.3, PL e)
Machine Safety
IEC 61000-6-7:2014
EMC
EN 61000-6-7:2015
IEC/EN 61326-3-1:2017
IEC 61800-5-1:2007/AMD1:2016
LVD
EN 61800-5-1:2007/A1:2017
Note:
SIL = Safety Integrity Level.

Safe Disable Specifications

The Safe Disable input provides the stop function that complies with "Safe Torque Off" as specified by IEC/EN
61800-5-2. The Safe Disable input meets the requirements of ISO/EN ISO 13849-1 and IEC/EN 61508. It also has
a safety status monitor to detect safety circuit errors.
When you install the drive as a component in a system, you must make sure that the system complies with the
applicable safety standards.
Input/Output
Response time from when the input opens to when the drive output stops
Response time from when the H1 and H2 terminal inputs open to when the EDM signal
operates
Failure probability in Less frequent operation request mode
Failure probability in Frequent operation request mode or continuous mode
Performance level
HFT (hardware fault tolerance)
Type of subsystem
MTTF
D
DCavg
Mission time
EDM = External Device Monitoring
PFD = Probability of Failure on Demand
180
Figure 5.20 TUV Mark
Table 5.21 Applied Safety Standards and Unified Standards
Table 5.22 Safe Disable Specifications
Item
Unified Standards
Description
• Input: 2
Safe Disable input (H1, H2)
Signal ON level: 18 Vdc to 28 Vdc
Signal OFF level: -4 Vdc to +4 Vdc
• Output: 1
MFDO safety monitor output for external device monitor (EDM)
3 ms or less
30 ms or less
PFD = 1.38E
-5
-9
PFH = 3.35E
The Safe Disable input complies with the performance level requirements of EN ISO
13849-1.
N = 1
Type B
High
Medium
10 years
SIEPCYEUOQ2V01A Q2V Technical Manual

Advertisement