Setting Value
Function
3E
SCBraking NO
3F
SCBraking NC
40
KEB Thru1 NC
41
KEB Thru1 NO
42
KEB Thru2 NC
43
KEB Thru2 NO
44
Field weakening
45
ASR Gain Switch
46
ASR I Reset
60
Timer Fn Input
61
Motor 2 Select
62
Up Command
63
Down Command
65
Up2 Command
66
Dw2 Command
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets operation of Short Circuit Braking (N.O.).
ON : Short Circuit Braking is enabled.
OFF : Normal operation
Note:
When A1-02 = 8 [Control Method = EZ Vector], this function is available only when you use a PM motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of Short Circuit Braking (N.C.).
ON : Normal operation
OFF : Short Circuit Braking is enabled.
Note:
When A1-02 = 8 [Control Method = EZ Vector], this function is available only when you use a PM motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-01
[Field Weak Level] and d6-02 [Field Weak FqLimit] when the input terminal is activated.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to switch the ASR proportional gain set in C5-01 [ASR PGain 1] and C5-03 [ASR PGain 2].
ON : C5-03
OFF : C5-01
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 39].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
ON : Operate motor 2
OFF : Operate motor 1
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command to use a push button switch to increase the drive frequency reference. You must also set Setting
63 [Down Command].
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set Setting
62 [Up Command].
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to increase the frequency reference bias value to accelerate the motor when the terminal is
activated. Set this function and H1-xx = 66 [Dw2 Command] together.
Note:
When you use this function, use d4-08 and d4-09 [Up/Dw2 Bias Upper Limit and Up/Dw2 Bias Lower Limit]
to set the optimal bias limit value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to decrease the frequency reference bias value to decelerate the motor when the terminal is
activated. Set this function and H1-xx = 65 [Up2 Command] at the same time.
Note:
When you use this function, use d4-08 and d4-09 [Up/Dw2 Bias Lower Limit] to set the optimal bias limit
value.
Description
11.9 H: TERMINALS