12.9

n: SPECIAL

n parameters set these functions:
• Function to prevent hunting
• High-slip braking
• Motor line-to-line resistance online tuning
• Fine-tune the parameters that adjust motor control

n1: HUNTING PREVENTION

The Hunting Prevention function will not let low inertia or operation with a light load cause hunting. Hunting
frequently occurs when you have a high carrier frequency and an output frequency less than 30 Hz.
n1-01: HuntPrev Selection
No.
Name
(Hex.)
HuntPrev Selection
n1-01
(0580)
Note:
When you replace a V1000-series drive with a Q2V drive, set n1-01 = 1 [HuntPrev Selection = Enabled].
When drive response is more important than the decrease of motor vibration, disable this function.
0 : Disabled
1 : Enabled
2 : Enabled (High Carrier)
n1-02: HuntPrev Gain Setting
No.
Name
(Hex.)
HuntPrev Gain Setting
n1-02
(0581)
Expert
Adjust this parameter in these conditions:
• When n1-01 = 1, 2 [HuntPrev Selection = Enabled, Enabled (High Carrier)], if oscillation occurs when you
operate a motor with a light load, increase the setting value in 0.1-unit increments.
• When n1-01 = 1, 2, if the motor stalls, decrease the setting value in 0.1-unit increments.
n1-03: HuntPrev Time Constant
No.
Name
(Hex.)
HuntPrev Time Constant
n1-03
(0582)
Expert
Adjust this parameter in these conditions:
• Load inertia is large: Increase the setting value. If the setting value is too high, response will be slower. Also,
there will be oscillation when the frequency is low.
• Oscillation occurs at low frequencies: Decrease the setting value.
n1-05: HuntPrev Gain Reverse Mode
No.
Name
(Hex.)
HuntPrev Gain Reverse
n1-05
Mode
(0530)
Expert
Note:
When you set n1-05 = 0, the value set in n1-02 [HuntPrev Gain Setting] is effective when the motor rotates in reverse.
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to prevent hunting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the performance of the hunting prevention function. Usually it is not necessary to change this
parameter.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the primary delay time constant of the hunting prevention function. Usually it is not
necessary to change this parameter.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the performance of the hunting prevention function. This parameter adjusts Reverse run.
Usually it is not necessary to change this parameter.
Description
Description
Description
Description

12.9 n: SPECIAL

Default
(Range)
0
( 0 to 2 )
Default
(Range)
1.00
(0.00 - 2.50)
Default
(Range)
Determined by o2-04
(0 - 500 ms)
Default
(Range)
0.00
(0.00 - 2.50)
12
675