11.4 b: APPLICATION

11.4

b: APPLICATION

b1: OPERATION MODE SELECT

No.
Name
(Hex.)
b1-01
Freq. Ref. Sel. 1
(0180)
b1-02
Run Comm. Sel 1
(0181)
b1-03
Stopping Method
Selection
(0182)
b1-04
Reverse Operation
Selection
(0183)
b1-06
Double Scan DI Inputs
Select
(0185)
b1-07
LO/RE Run Selection
(0186)
b1-08
RUN@PRG Mode
Selection
(0187)
b1-14
Phase Order Selection
(01C3)
b1-15
Freq. Ref. Sel. 2
(01C4)
318
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Modbus
3 : Option PCB
4 : Pulse Train Input
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input method for the Run command.
0 : Keypad
1 : Analog Input
2 : Modbus
3 : Option PCB
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the method to stop the motor after removing a Run command or entering a Stop
command.
Note:
When A1-02 = 5, 6, 8 [Control Method = PM OLVector, PM AOLVector, EZ
Vector], the setting range is 0, 1, 3.
0 : Ramp->Stop
1 : Coast->Stop
2 : DC Inj->Stop
3 : Timed Coast->Stop
9 : Distance Stop
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the reverse operation function. Disable reverse operation in fan or pump
applications where reverse rotation is dangerous.
0 : Enabled
1 : Disabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the number of times that the drive reads the sequence input command to prevent
malfunction because of noise.
1 : Single Scan
2 : Double Scan
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets drive response to an existing Run command when the drive receives a second Run
command from a different location.
1 : Cycle RUN
2 : Accept RUN
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the conditions for the drive to accept a Run command entered from an external
source when using the keypad to set parameters.
1 : NoRUN@Program
2 : RUN@Program
3 : Program@Stop only
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can
align the Forward Run command from the drive and the forward direction of the motor
without changing wiring.
0 : Standard
1 : Phase Order Switch
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the input method for frequency reference 2.
0 : Keypad
1 : Analog Input
2 : Modbus
3 : Option PCB
4 : Pulse Train Input
Default
(Setting Range)
1
(0 - 4)
1
(0 - 3)
0
(0 - 3, 9)
0
(0, 1)
2
(1, 2)
1
(1, 2)
1
(1 - 3)
0
(0, 1)
0
(0 - 4)
SIEPCYEUOQ2V01A Q2V Technical Manual