D2: Reference Limits; D3: Jump Frequency - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

11.6 d: REFERENCE
No.
Name
(Hex.)
d1-13
Reference 13
(028E)
RUN
d1-14
Reference 14
(028F)
RUN
d1-15
Reference 15
(0290)
RUN
d1-16
Reference 16
(0291)
RUN
d1-17
Jog Reference
(0292)
RUN

d2: REFERENCE LIMITS

No.
Name
(Hex.)
d2-01
FRef Upper Limit
(0289)
d2-02
FRef Lower Limit
(028A)
d2-03
Analog FRef Lower
Limit
(0293)

d3: JUMP FREQUENCY

No.
Name
(Hex.)
d3-01
Jump Frequency 1
(0294)
d3-02
Jump Frequency 2
(0295)
332
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency reference in the units from o1-03 [FrqDisplay Unit Selection].
Note:
When A1-02 = 6 [Control Method = PM AOLVector], the default setting is o1-03 =
1 [0.01% (100%=E1-04)].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency reference in the units from o1-03 [FrqDisplay Unit Selection].
Note:
When A1-02 = 6 [Control Method = PM AOLVector], the default setting is o1-03 =
1 [0.01% (100%=E1-04)].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the frequency reference in the units from o1-03 [FrqDisplay Unit Selection].
Note:
When A1-02 = 6 [Control Method = PM AOLVector], the default setting is o1-03 =
1 [0.01% (100%=E1-04)].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the frequency reference in the units from o1-03 [FrqDisplay Unit Selection].
Note:
When A1-02 = 6 [Control Method = PM AOLVector], the default setting is o1-03 =
1 [0.01% (100%=E1-04)].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Jog frequency reference in the units from o1-03 [FrqDisplay Unit Selection].
Set H1-xx = 6 [MFDI Function Select = Jog Reference] to use the Jog frequency
reference.
Note:
When A1-02 = 6 [Control Method = PM AOLVector], the default setting is o1-03 =
1 [0.01% (100%=E1-04)].
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets maximum limit for all frequency references. The maximum output frequency is
100%.
Note:
Parameter A1-02 [Control Method] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZ Vector]: E1-04 [Max Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets minimum limit for all frequency references. The maximum output frequency is
100%.
Note:
Parameter A1-02 [Control Method] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZ Vector]: E1-04 [Max Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the lower limit for the master frequency reference (the first frequency of the multi-
step speed reference) as a percentage. The maximum output frequency is 100%.
Note:
Parameter A1-02 [Control Method] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZ Vector]: E1-04 [Max Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the median value of the frequency band that the drive will avoid.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the median value of the frequency band that the drive will avoid.
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
6.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
100.0%
(0.0 - 110.0%)
0.0%
(0.0 - 110.0%)
0.0%
(0.0 - 110.0%)
Default
(Range)
0.0 Hz
(Determined by A1-02)
0.0 Hz
(Determined by A1-02)
SIEPCYEUOQ2V01A Q2V Technical Manual
Ref.
513
513
513
513
513
Ref.
514
514
514
Ref.
515
515

Advertisement