No.
Name
(Hex.)
L6-04
Trq Det2 Select
(04A4)
L6-53
Trq Det2 Type
(04CF)
L6-54
Trq Det2 Action
(04D0)
L6-55
Trq Det2 Condition
(04D1)
L6-05
Trq Det2 Level
(04A5)
L6-06
Trq Det2 Time
(04A6)
L6-07
Trq Detect Filter Time
(04E5)
L6-08
MechF Enable
(0468)
L6-56
MechF Action
(04D2)
L6-57
MechF AbsSpeed
(04D3)
L6-58
MechF Method
(04D4)
L6-09
MechFatigue Speed
Detect Level
(0469)
L6-10
MechFatigue Delay
Time
(046A)
L6-11
MechFatigue Hold Off
Time
(046B)
SIEPCYEUOQ2V01A Q2V Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Enables overtorque and undertorque detection and the operation of drives (operation
status) after detection.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the speed range that detects overtorque and undertorque.
0 : At Overload
1 : At Underload
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets operation of drives (operation status) after detection.
0 : Alarm
1 : Fault
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets operation of drives (operation status) after detection.
0 : At Speed Agree
1 : During Run
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive
rated output current = 100% value. In vector control, motor rated torque = 100% value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the detection time for Overtorque/Undertorque Detection 2.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the time constant for a primary filter to the torque reference or to the output current
used to detect overtorque/undertorque.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Enables mechanical deterioration detection and how the drive operates (operation
status) after detection.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the speed where the drive detects mechanical deterioration and how the drive
operates (operation status) after detection. Only available when L6-08 = 1 [MechF
Enable = Enabled].
0 : Alarm
1 : Fault
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the speed where the drive detects mechanical deterioration and how the drive
operates (operation status) after detection. Only available when L6-08 = 1 [MechF
Enable = Enabled].
0 : Spd Absolute
1 : Spd Signed
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the speed where the drive detects mechanical deterioration and how the drive
operates (operation status) after detection. Only available when L6-08 = 1 [MechF
Enable = Enabled]. Use parameter L6-57 [MechF AbsSpeed] to either use absolute
speed or signed speed value.
0 : Spd>L6-09
1 : Spd<L6-09
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the speed level where the drive will operate the mechanical deterioration detection
function, as a percentage of the Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZ Vector]: E1-04 [Max Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time for mechanical deterioration detection.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time that the drive will start mechanical deterioration detection triggered by the
cumulative operation time of the drive.
11.10 L: PROTECTION
Default
Ref.
(Range)
0
663
(0, 1)
0
665
(0, 1)
0
665
(0, 1)
0
665
(0, 1)
150%
663
(0 - 300%)
0.1 s
663
(0.0 - 10.0 s)
0 ms
663
(0 - 1000 ms)
0
663
(0, 1)
0
665
(0, 1)
0
665
(0, 1)
0
665
(0, 1)
110.0%
664
(-110.0 - 110.0%)
0.1 s
664
(0.0 - 10.0 s)
0 h
664
(0 - 65535 h)