12.3 C: TUNING
1 : High Perf 1
C5-39: ASR Delay Time 2
No.
Name
(Hex.)
C5-39
ASR Delay Time 2
(030D)
If you have a load with low rigidity or if oscillation is a problem, increase this setting in 0.01 unit increments.

C6: DUTY AND CARRIER

C6 parameters are used to set the selection of drive duty rating, selection of carrier frequency, and upper and
lower limits of carrier frequencies.
C6-01: ND/HD Duty Selection
No.
Name
(Hex.)
C6-01
ND/HD Duty Selection
(0223)
0 : HD Rating
The overload tolerance is 150% of the rated output current for 60 seconds.
1 : ND Rating
The overload tolerance is 110% of the rated output current for 60 seconds.
There are two types of load ratings for this product depending on the load characteristics of the application: Heavy
Duty Rating (HD) and Normal Duty Rating (ND).
The drive rated output current, overload tolerance, and acceleration stall prevention level change when the duty
rating changes. Set the drive to agree with the duty rating of the selected drive capacity. In HD, the tolerance is
150% overload for 60 seconds. In ND, the tolerance is 110% overload for 60 seconds. The rated output current for
ND drives is higher than the rated output current for HD drives. Refer to
V Class) on page
292,
Model Specifications (Single-Phase 200 V Class) on page
(Three-Phase 400 V Class) on page 296
Table 12.23 Differences between Heavy Duty Rating and Normal Duty Rating
Item
C6-01 Setting
Load Characteristics
Application
Overload Tolerance
Stall Prevent Level during Accel
Stall Prevent Level during Run
Carrier Frequency
504
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the filter time constant used when the torque reference is output from ASR. Usually it is not
necessary to change this parameter.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the drive duty rating.
for more information about the rated output current.
Heavy Duty Rating (HD)
0
A high overload tolerance is necessary during start up, acceleration,
deceleration, and equivalent conditions.
• Extruder
• Conveyor
• Cranes and hoists
• Constant torque or high overload capacity are necessary.
150% - 60 seconds
150%
150%
2 kHz
Description
Description
Model Specifications (Three-Phase 200
295, and
Normal Duty Rating (ND)
Overload tolerance is not necessary.
• Fan
• Pump
• Blower
SIEPCYEUOQ2V01A Q2V Technical Manual
Default
(Range)
0.000 s
(0.000 - 0.500 s)
Default
(Range)
0
(0, 1)
Model Specifications
1
110% - 60 seconds
120%
120%
2 kHz Swing-PWM