5.2 European Standards
5.
Connect an AC reactor or DC reactor to decrease harmonic distortion. Refer to
page 165
to select a DC reactor.
Note:
• To maintain compliance with EN 61000-3-2 on drive models 2001 to 2006, 4001 to 4004, install a DC reactor.
Ground Wiring
WARNING! Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you touch the
internal components of an energized drive, it can cause serious injury or death.
WARNING! Electrical Shock Hazard. Ground the neutral point on the power supply of drive models 2xxxE, BxxxE, and 4xxxE to
comply with the EMC Directive before you turn on the EMC filter or if there is high resistance grounding. If the EMC filter is
switched ON without the neutral point being grounded or if there is high resistance grounding, it can cause death or serious
injury.
Enable the Internal EMC Filter
On drive models 2xxxE, BxxxE, and 4xxxE, move the screw or screws to turn ON and OFF (enable and disable)
the EMC filter.
Make sure that the symmetric grounding network is applied, and install the screw or screws in the ON position to
enable the built-in EMC filter in compliance with the EMC Directive. The EMC filter switch screw or screws are
installed in the OFF position by default.
WARNING! Electrical Shock Hazard. Disconnect all power to the drive, wait for the time specified on the warning label, and
check the drive for dangerous voltages before you remove covers or touch EMC filter screws. If you touch the screws when
there are dangerous voltages, it will cause serious injury or death.
WARNING! Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you touch the
internal components of an energized drive, it can cause serious injury or death.
WARNING! Electrical Shock Hazard. Ground the neutral point on the power supply of drive models 2xxxE, BxxxE, and 4xxxE to
comply with the EMC Directive before you turn on the EMC filter or if there is high resistance grounding. If the EMC filter is
switched ON without the neutral point being grounded or if there is high resistance grounding, it can cause death or serious
injury.
WARNING! Electrical Shock Hazard. Connect the ground cable correctly. If you touch electrical equipment that is not grounded,
it can cause serious injury or death.
NOTICE: To disable the internal EMC filter, move the screws from ON to OFF and then tighten to the specified torque. If you
fully remove the screws or tighten the screws to an incorrect torque, it can cause drive failure.
NOTICE: Move the EMC switch screw or screws to the OFF position for networks that are not symmetrically grounded. If the
screws are not in the correct position, it can cause damage to the drive.
NOTICE: When you use the drive with a non-grounding, high-resistance grounding, or asymmetric-grounding network, put the
EMC Filter screw or screws in the OFF position to disable the built-in EMC filter. Failure to obey the instructions can damage the
drive.
Type of Grounding
Grounded at the corner of the delta connection
Grounded at the middle of the side
160
Figure 5.7 Symmetric Grounding
Table 5.8 Asymmetric Grounding Networks
DC Reactor Selection on
Diagram
SIEPCYEUOQ2V01A Q2V Technical Manual