Omron Q2V Series Technical Manual page 241

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

Code
Name
EF0
Option Card External Fault
Note:
• The drive detects this error if the alarm function on the external device side is operating.
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 4 [MFDO Function Select = Alarm] will activate.
• If the drive detects this error, it will operate the motor as specified by the stopping method set in F6-03 [Comm Ext Flt Select (EF0)].
Code
Name
EF1
External Fault (Terminal DI1)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 4 [MFDO Function Select = Alarm] will activate.
Code
Name
EF2
External Fault (Terminal DI2)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm] will activate.
Code
Name
EF3
External Fault (Terminal DI3)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm] will activate.
Code
Name
EF4
External Fault (Terminal DI4)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm] will activate.
Code
Name
EF5
External Fault (Terminal DI5)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm] will activate.
Code
Name
EF6
External Fault (Terminal DI6)
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm] will activate.
SIEPCYEUOQ2V01A Q2V Technical Manual
Causes
The communication option card received an
external fault from the controller.
A programming error occurred on the controller
side.
Causes
MFDI terminal DI1 caused an external fault through
an external device.
The wiring is incorrect.
External Fault [H1-01 = 2C to 2F] is set to MFDI
terminal DI1, but the terminal is not in use.
Causes
MFDI terminal DI2 caused an external fault through
an external device.
The wiring is incorrect.
External Fault [H1-02 = 2C to 2F] is set to MFDI
terminal DI2, but the terminal is not in use.
Causes
MFDI terminal DI3 caused an external fault through
an external device.
The wiring is incorrect.
External Fault [H1-03 = 2C to 2F] is set to MFDI
terminal DI3, but the terminal is not in use.
Causes
MFDI terminal DI4 caused an external fault through
an external device.
The wiring is incorrect.
External Fault [H1-04 = 2C to 2F] is set to MFDI
terminal DI4, but the terminal is not in use.
Causes
MFDI terminal DI5 caused an external fault through
an external device.
The wiring is incorrect.
External Fault [H1-05 = 2C to 2F] is set to MFDI
terminal DI5, but the terminal is not in use.
Causes
MFDI terminal DI6 caused an external fault through
an external device.
The wiring is incorrect.
External Fault [H1-06 = 2C to 2F] is set to MFDI
terminal DI6, but the terminal is not in use.
7.5 Minor Faults/Alarms
Possible Solutions
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input from the controller.
Examine the operation of the controller program.
Possible Solutions
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI1.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI2.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI3.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI4.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI5.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI6.
Correctly set the MFDI.